Light Intensity with Temp, Humidity Trans Op Instr Datasheet by Seeed Technology Co., Ltd

View All Related Products | Download PDF Datasheet
Light intensity with temperature and humidity transmitter operation instructionV1.3
Shandong RenKe Control Technology Co.,Ltd. www.temperaturehumiditysensor.com
1
RS-GZ-N01
RS-GZWS-N01
Light intensity with temperature
and humidity transmitter
operation instruction
Range:0-200000lux
Document versionV1.3
Light intensity with temperature and humidity transmitter operation instructionV1.3
Shandong RenKe Control Technology Co.,Ltd. www.temperaturehumiditysensor.com
2
Context
1. Product Introduction.............................................................................................................3
1.1 Product summary.......................................................................................................... 3
1.2 Function feature............................................................................................................ 3
1.3 Main technology parameter.......................................................................................... 3
1.4 System frame diagram.................................................................................................. 4
2. Device Installation Instruction................................................................................................4
2.1 Check before the device installation.............................................................................4
2.2 Joggle instruction.......................................................................................................... 4
2.3 Field wiring instructions............................................................................................... 5
3. Configuration Software Installation and Application............................................................. 5
3.1 Software selection...................................................................................................... 5
3.2 Parameter setting...........................................................................................................5
4.Communication Agreement..................................................................................................... 6
4.1 Communication basic parameter...................................................................................6
4.2 The concept of data frame format.................................................................................7
4.3 Register address............................................................................................................ 7
4.4 Communication agreement example and explaining....................................................8
4.4.1 reading the value of temperature and humidity in device address 0x01........... 8
4.4.2 reading the value of light intensity in device address 0x01(Unit is 100Lux)... 8
4.4.3 reading the value of light intensity in device address 0x01(Unit is 1Lux)....... 9
4.4.4 reading the value of light intensity with temperature and humidity in device 9
5. Common Problem and Solution............................................................................................10
5.1 Device can not be connected with PLC or computer................................................. 10
6. Contact Information.............................................................................................................. 11
7. Document History................................................................................................................. 11
8. Shell Size............................................................................................................................... 11
.1an
Light intensity with temperature and humidity transmitter operation instructionV1.3
Shandong RenKe Control Technology Co.,Ltd. www.temperaturehumiditysensor.com
3
1. Product Introduction
1.1 Product summary
This product is widely applied in agricultural greenhouses or flower cultivation where
needs the temperature and humidity monitor or light intensity .The three parts about input power
supply, temperature measurement unit and signal output of sensor are completely isolated. Safe
and reliable, beautiful appearance, easy installation.
1.2 Function feature
This product uses high sensitivity probe.The output signal is stable.This product powered by
10V-30V wide voltage, complete specifications and convenient to install.
1.3 Main technology parameter
Power supply voltagedefault
10-30VDC
Maximum power dissipation
RS485 Output
0.4W
Degree of accuracydefault
Humidity
±3%RH(5%RH~95%RH,25)
Temperature
±0.5℃(25℃)
Light intensity
±7%(25)
Range of light intensity
0-200000Lux
Range of temperature
and humidity
-20~+60℃,0%RH~80%RH
Long-term stability
Humidity
Temperature
Light intensity
Reaction time
Humidity
Temperature
Light intensity
Output signal
RS485
About model
RS-GZ-N01-2-0-20w(Light intensity)
RS-GZWS-N01-2-20w(Light intensity with temperature and humidity)
AC 2 2 (Wei 485 wire
Light intensity with temperature and humidity transmitter operation instructionV1.3
Shandong RenKe Control Technology Co.,Ltd. www.temperaturehumiditysensor.com
4
1.4 System frame diagram
2. Device Installation Instruction
2.1 Check before the device installation
Device list:
One transmitter equipment
Certificate, warranty card, and after sales service card and so on
one 12V/2A waterproof powerselect
USB transfer to 485select
485 terminal resistanceselect
2.2 Joggle instruction
Range 10V-30V of wide voltage is available in power input, the A wire and B wire can not be
connected contrary when connecting to 485 signal, and the address among several devices on the
total wire can not be conflicted.
Line color
Description
Power
Brown
Power supply is (10 ~ 30V
DC)
Black
Power supply negative
Communication
Yellow
485-A
Blue
485-B
«sagging 3317.“. 14, + $311! mm (mm an m) j Prolific usa»ta—s.ri.1 Comm rm (cum) 9 USE Serial Pm (com) ,9 uss—smu. arms (cums)
Light intensity with temperature and humidity transmitter operation instructionV1.3
Shandong RenKe Control Technology Co.,Ltd. www.temperaturehumiditysensor.com
5
2.3 Field wiring instructions
When multiple 485 devices are connected to the same bus,site wiring has specific
requirements,details please refer to the package,details please refer to the "485 equipment site
wiring manual.
3. Configuration Software Installation and Application
3.1 Software selection
Opening the datagram, and choosing “test software” ---- “485 parameter setting software”
and finding out and opening it.
3.2 Parameter setting
select the right COM port (“my computer——propertiesdeceive manager——Port)
and check the COM port from the Port, the name of several different kinds of 485 transmitter
drive
connect with only one device and be powered, and click “test the baud rate” of the
software to test the device baud rate and address, the default baud rate is 4800bit/s and default
address is 0x01
change the address and baud rate based on the application requirement, and meanwhile the
current situation of the device function can be checked
if the test is not success, please check the device wring and 485 drive installation situation
again.
Seriel Pun Num' cam - -;. Jew: Devi ce Address: Device Band Rate: 4300 tt' Temperature Value: m Humidity Value: Wiley Leak Status: TWTTTTJ Power Failure Status: L, “M I“ Search Resuk 5025 SW: tth - Device Addresszl Band Rate14800 Remote Sign Humid“. A Humdity l tempemure Upper Limit: Imperemre Lower Limit: Humidity Hysuresis: Tempemure Hysteresis: Humidity Adjust: Temperature Adjust: TWTTTT LLLL LCD Davin: Cnntrnl Mode‘ A" J ' "‘ ‘. Wit-lass Rcctivtr Pu“ SM“
Light intensity with temperature and humidity transmitter operation instructionV1.3
Shandong RenKe Control Technology Co.,Ltd. www.temperaturehumiditysensor.com
6
4.Communication Agreement
4.1 Communication basic parameter
Code
8 bit binary system
Data Bit
8 bit
Odd-even Revi-sio
n Bit
None
Stop Bit
1bit
Light intensity with temperature and humidity transmitter operation instructionV1.3
Shandong RenKe Control Technology Co.,Ltd. www.temperaturehumiditysensor.com
7
Incorrect Revis-io
n
CRCRedundant cyclic codes
Baud Rate
2400bit/s, 4800bit/s, 9600 bit/s options, the factory default 4
800bit/s
4.2 The concept of data frame format
Apply Modbus-RTU communication rulesthe format below
Initial structure 4 byte time
Address code = 1 byte
Function code = 1 byte
Data area = N byte
Incorrect revision = 16 byte CRC code
Ending structure 4 byte time
Address codethe address of the transmitterand will be the only (factory default 0x01) in the
communication net..
Function code the order function orders from host computer, this transmitter only uses
function code 0x03(reading register date).
Data area data area is the specific communication data, attention16bits data high byte in
front!
CRC codetwo byte revision code.
Main computer enquires frame structure
Add
ressCode
Functi
on Code
Register Ori
gin
Address
Register Le
ngth
Revision Code
in Low Pos
ition
Revision Co
de
in High Posi
tion
1byt
e
1byte
2bytes
2bytes
1byte
1byte
Accessorial computer replying frame structure
Addr
ess Code
Func
tion Cod
e
Effective
ness Byte N
O.
Data
Area One
Data Area
Two
Data Ar
ea N
Revision
Code
1byt
e
1byt
e
1byte
2bytes
2bytes
2bytes
2bytes
4.3 Register address
Register Address
PLC or
Configuration Address
Content
Operation
4.4.2 reading the value of light intensity in device address 0x01(Unit is lflflLux)
Light intensity with temperature and humidity transmitter operation instructionV1.3
Shandong RenKe Control Technology Co.,Ltd. www.temperaturehumiditysensor.com
8
0000 H
40001
Temperature
Read only
0001 H
40002
Humidity
Read only
0002 H
40003
Light intensityUnit is
1Lux
Read only
0003 H
40004
0006 H
40007
Light intensity
Unit is 100Lux
Read only
4.4 Communication agreement example and explaining
4.4.1 reading the value of temperature and humidity in device address 0x01
enquiry frame
Address
Code
Function
Code
Origin
Address
Data Leng
th
Revision
Code
in Low
Position
Revision
Code
in High
Position
0x01
0x03
0x00 0x0
0
0x00 0x02
0xC4
0x0B
Replication frame(when reading temperature is -10.1℃,humidity is 65.8%RH
Ad
dress C
ode
Fun
ction Co
de
Return By
te
Number
Humi
dity
Numb
er
Tempe
rature
Numb
er
Revision
Code in Lo
w
Position
Revision Co
de
in High
Position
0x0
1
0x0
3
0x04
0x02
0x92
0xFF
0x9B
0x5A
0x3D
Temperature calculation
When temperature is under 0 , the temperature date will be updated in complement code.
TemperatureFF9B H(Hexadecimal)= -101 => temperature = -10.1
Humidity calculation
Humidity292 H (Hexadecimal)= 658 => humidity = 65.8%RH
4.4.2 reading the value of light intensity in device address 0x01(Unit is 100Lux)
Address
Code
Function
Code
Origin
Address
Data Leng
th
Revision C
ode
in Low
Position
Revision
Code
in High
Position
Light intensity with temperature and humidity transmitter operation instructionV1.3
Shandong RenKe Control Technology Co.,Ltd. www.temperaturehumiditysensor.com
9
0x01
0x03
0x00 0x06
0x00 0x01
0x64
0x0B
Enquiry frame
Replication frame(when reading light intensity is 132800 Lux
Addres
s
Code
Function
Code
Return Byt
e
Number
Data Area
Revision C
ode in Low
Position
Revision
Code in Low
Position
0x01
0x03
0x02
0x05 0x30
0xBB
0x00
Calculation instructions: (Unit is 100Lux)
0530 H(Hexadecimal)= 1328=> Light intensity=132800 Lux
4.4.3 reading the value of light intensity in device address 0x01(Unit is 1Lux)
Enquiry frame
Address
Code
Function
Code
Origin
Address
Data Leng
th
Revision C
ode
in Low
Position
Revision
Code
in High
Position
0x01
0x03
0x00 0x02
0x00 0x02
0x65
0xCB
Replication frame(when reading light intensity is 132800 Lux
Addr
ess
Code
Functi
on
Code
Return
Byte
Number
Data Area
Revision
Code in Lo
w
Position
Revisio
n Code in L
ow
Position
0x01
0x03
0x04
0x00 0x02
0x06 0xC0
0x58
0x03
Calculation instructions: (Unit is 100Lux)
206C0 H(Hexadecimal)= 132800=> Light intensity=132800 Lux
4.4.4 reading the value of light intensity with temperature and humidity in device
address 0x01(Unit is 100Lux)
Enquiry frame
Address
Code
Function
Code
Origin
Address
Data Leng
th
Revision
Code
in Low
Position
Revision
Code
in High
Position
0x01
0x03
0x00 0x00
0x00 0x07
0x04
0x08
Replication frame(when reading temperature is -10.1℃,humidity is 65.8%RH,
10
Light intensity with temperature and humidity transmitter operation instructionV1.3
Shandong RenKe Control Technology Co.,Ltd. www.temperaturehumiditysensor.com
10
light intensity is 1328 Lux
4.4.5 reading the value of light intensity with temperature and humidity in device
address 0x01(Unit is 1Lux)
Enquiry frame
Address
Code
Function
Code
Origin
Address
Data Leng
th
Revision
Code
in Low
Position
Revision
Code
in High
Position
0x01
0x03
0x00 0x00
0x00 0x04
0x44
0x09
Replication frame(when reading temperature is -10.1℃,humidity is 65.8%RH,
light intensity is 200000 Lux
Ad
dress
Co
de
Fun
ction
Co
de
Return
Byte
Number
Humi
dity
Number
Temper
ature
Number
Light
intensity
CRC
0x01
0x03
0x08
0x02 0x92
0x80 0x65
0x00 0x03
0x0D 0x40
0x01 0x6F
5. Common Problem and Solution
5.1 Device can not be connected with PLC or computer
Reasons possible:
1) Several COM ports in the computer, the port be chosen is incorrect.
2) The device address is wrong, or some device addresses are repeat.(all factory defaults are
1).
3) Baud rate, revision mode, data position and stop position are wrong.
4) The main computer and polling interval is too small and time waiting for replying is too
short, and
all need to set over 200ms.
5) The 485 general wire is broken or the A wire and B wire are connected in the wrong side.
6) Too many devices or too long wires, the power need to be chosen nearby, add 485
intensifier, and add 120Ω
Ad
dress C
ode
Fun
ction Co
de
Return B
yte
Number
Humid
ity
Number
Temper
ature
Number
**
Light
intensity
CRC
0x01
0x03
0x0E
0x02 0x92
0x80 0x65
Fill 00
0x05 0x30
0xC4 0x33
Light intensity with temperature and humidity transmitter operation instructionV1.3
Shandong RenKe Control Technology Co.,Ltd. www.temperaturehumiditysensor.com
11
terminal electric resistance.
7) The driver of USB transfer to 485is not installed or damaged.
8) The device is broken.
6. Contact Information
Shandong Renke Control Technology Co., Ltd.
Post code250101
Tel+86-531-58720832
Fax+86-531-67805165
Website address: www.temperaturehumiditysensor.com
7. Document History
V1.0 Document building.
V1.1 Add a variety of card rail shell.
V1.2 Increase wiring rules and solutions to common problems.
8. Shell Size
Total size:110×85×44mm

Products related to this Datasheet

LIGHT INTENSITY TRANSMITTER (0-2